Iso 8 class 100 000 0 005 0 041 1 8 5 48.
Iso class 1 clean room.
Iso 6 class 1 000 0 127 0 203 25 40 150 240.
A cleanroom must have less than 35 200 000 particles 0 5 micron per cubic meter and 20 hepa filtered air changes per hour.
Iso 7 class 10 000 0 051 0 076 10 15 60 90.
The former applies to clean rooms in general see table below.
The lower the iso class the more stringent the requirements for keeping particles and contamination to the acceptable levels of the room class.
However class will greatly impact design considerations such as filtration hvac requirements and other design elements.
The class defines a minimum cleanliness level not a specific design.
As of november 29th 2001 the federal standard 209e has been replaced with iso 14644 1.
The latter to cleanrooms where biocontamination may be an issue.
Iso 14644 1 and older standard fs 209e determine class by the concentration levels of particles.
Ordinary room air is around class 1 000 000 or iso 9.
Depending on the iso class there are required averages for the number of air changes per hour.
By comparison a typical office space would be 5 10 times more dirty.
Iso 6 cleanroom class 1 000 in theory for an entire room to reach iso 6 air cleanliness you need to enter the cleanroom via an iso 8 ante room then go through an iso 7 to finally get into the iso 6 as shown in the image.
Iso 14644 1 and iso 14698.
Iso class 1 iso class 2 and iso class 3 will require 500 to 750 air changes per hour.
So for example an iso class 5 cleanroom has at most 105 100 000 particles per m.
The equivalent fed standard is class 100 000 or 100 000 particles per cubic foot.
The number of air changes per hour refers to the volume of filtered air in a single hour divided by the cleanroom volume.
The recommended air changes per hour for an iso class 1 clean room is 500 750 and the ceiling coverage should be 80 100.
In reality however you can reach an iso 6 clean room with 1 recommendation is 2 airlock.
Class iso 146144 1 federal standard 209e average airflow velocity m s ft min air changes per hour ceiling coverage.
Iso 14644 1 and iso 14698 are non governmental standards developed by the international organization for standardization iso.
Iso 5 class.
Small numbers refer to iso 14644 1 standards which specify the decimal logarithm of the number of particles 0 1 µm or larger permitted per cubic metre of air.
Iso class 1 the cleanest cleanroom is iso 1 used in industries such as life sciences and electronics that require nanotechnology or ultra fine particulate processing.
The particles range in size from 1 5 microns µm.